West Bengal Pollution Control Board

Kankinara Laboratory

Panpore More, Kalyani Expressway, Vill. Panpur, P.O. Narrayanpur, Dist: 24-Parganas (N), Pin 743 126,(033) 2502-1189



Station: Ganga at Palta, West Bengal River Basin: GANGA CPCB Station Code: 1054
Sample Date: 19/08/2020 Sample Time: 17:02  
Human Activities: Bathing & washing Weather: Cloudy Water Body: Ganga
Frequency Of Monitoring: Monthly Use Based Class: B Approximate Depth(Bottom/Table): 3.00 m 
Color & Intensity: Muddy Odour: Odour free Visible effluent discharge: None


Water Quality
Parameter Test Result Unit
  Potassium   4.8   mg/l
  Sodium   11.80   mg/l
  Total Alkalinity   113.47   mg/l
  E-coli   7000   MPN/100ml
  Temperature(Water)   30   ⁰C
  Total Suspended Solids(TSS)   112.00   mg/l
  Total Coliform   30000   MPN/100ml
  Turbidity   98.80   NTU
  Magnesium   7.33   mg/l
  Fecal Coliform   12000   MPN/100ml
  Fecal Streptococci   230   MPN/100ml
  Boron   BDL   mg/l
  Chloride   8.00   mg/l
  COD   12.53   mg/l
  Fluoride   0.55   mg/l
  Nitrite N   0.06   mg/l
  Total Fixed Solids(TFS)   212.00   mg/l
  Total Kjeldahl Nitrogen(TKN)      mg/l
  Ammonia-N   0.13   mg/l
  BOD   2.00   mg/l
  Conductivity   249.90   µs/cm
  Phenolpthalein Alkanity   NIL   mg/l
  Phosphate-P   0.12   mg/l
  Total Dissolved Solids(TDS)   142.00   mg/l
  pH   8.10   Unit
  Dissolved O2(DO)   4.40   mg/l
  Total Hardness as CaCo3   113.19   mg/l
  Nitrate-N   0.38   mg/l
  Calcium   33.20   mg/l
  Sulphate   33.21   mg/l